本表说明使用APF
PCS电力有源滤波器进行谐波治理的典型结果,该波形使用Tektronics示波器测得。 系统的谐波由带有直流链路电抗器的150马力交流电机产生,在系统的480V供电母线上接入一台APF PCS滤波补偿装置,它注入49A的补偿电流,使得供电电流的TDD%符合IEEE-519中的规定,同时电源的功率因素得到补偿,系统更加稳定。
|
|
补偿前
|
补偿后
|
|
谐波次数
|
%I
|
%
I
|
|
基波
|
100%
|
100%
|
|
3
|
0.038%
|
0.478%
|
|
5
|
31.66%
|
0.674%
|
|
7
|
11.48%
|
0.679%
|
|
9
|
0.435%
|
0.297%
|
|
11
|
7.068%
|
0.710%
|
|
13
|
4.267%
|
0.521%
|
|
15
|
0.367%
|
0.052%
|
|
17
|
3.438%
|
0.464%
|
|
19
|
2.904%
|
0.639%
|
|
21
|
0.284%
|
0.263%
|
|
23
|
2.042%
|
0.409%
|
|
25
|
2.177%
|
0.489%
|
|
27
|
0.293%
|
0.170%
|
|
29
|
1.238%
|
0.397%
|
|
31
|
1.740%
|
0.243%
|
|
33
|
0.261%
|
0.325%
|
|
35
|
0.800%
|
0.279%
|
|
37
|
1.420%
|
0.815%
|
|
39
|
0.282%
|
0.240%
|
|
41
|
0.588%
|
0.120%
|
|
43
|
1.281%
|
0.337%
|
|
45
|
0.259%
|
0.347%
|
|
47
|
0.427%
|
0.769%
|
|
49
|
1.348%
|
0.590%
|
|
%THD(I)
|
35.28%
|
2.670%
|
|
电气参数:
额定电压:208--480V, 允许偏差±10%。
频率:50/60Hz, ±3 Hz。
技术指标:
谐波电流 THD < 5%, TDD
< 5%, 谐波次数n=2~50。 谐波电压 THD < 5%, 谐波次数n=2~50。 滤波效果符合ANSI/IEEE
std 519-1992, GB/T14549-93。功率因素 COSФ >0.9。 响应速度 20 kHz。
使用环境:
运行温度:0°C~+40°C。 储存温度:-40°C~+65°C。
环境湿度:0%~95%, 不凝结。 海拔高度:2000M。
结 构:
标准结构:挂墙安装 落地安装 开放式底座(可选)
保 护:
输入熔断器:690V, 20000AIC。
冲击耐压:T 级。 容量:IEEE C62.41-1991。 过载能力:100% 额定值。
显示与控制:
显示屏:数字显示、2行, 每行20字母。 操作按键:运行、停止、设定、输入、上下滚屏。
指示灯:运行(绿)。 信息诊断:英语。
产品认证:
UL, CSA, EC。
|